CCHN is a trusted U.S. registered company in industrial automation & controls, CCHN's goal is helping saving your money by bypassing all kinds of local dealers/agents in buying industrial automation products from Chinese manufacturers directly. You will be enjoyed to get free tech support on how to choose, how to wire, how to commissioning with CCHN professional engineers. Shopping for your automation systems on CCHN one-stop online store now. The price on the website only for sample reference. for Mass order,please send the enquiry to us.

Blog

Foam cutting is a device for processing materials in the chemical industry such as foam and sponges. It mainly uses the high

...
CCHN Industry
 
Close
Shopping Categories
Search

CCHN Industry

CCHN is a trusted U.S. registered company in industrial automation & controls, CCHN's goal is helping saving your money by bypassing all kinds of local dealers/agents in buying industrial automation products from Chinese manufacturers directly. You will be enjoyed to get free tech support on how to choose, how to wire, how to commissioning with CCHN professional engineers. Shopping for your automation systems on CCHN one-stop online store now. The price on the website only for sample reference. for Mass order,please send the enquiry to us.

Blog

Foam cutting is a device for processing materials in the chemical industry such as foam and sponges. It mainly uses the high

...
30 hp VFD, 1-Phase 220V to 3-Phase 380V VFD
 
Close
Shopping Categories
Search

30 hp VFD, 1-Phase 220V to 3-Phase 380V VFD


$2455.97
30 hp VFD for sales, converts 1-phase 220V input to 3-phase 380V output, 45A rated current, 50Hz/ 60Hz input frequency, 0-400
SKU: GK3000-CS0220G
Free Shipping Worldwide
Delivery date: 6-12 days

Customize 30 hp (22kW) variable frequency drive at good price, with single phase 220 volt input and three phase 380 volt output, easy to operate and wire, convenient for you to use.

Specification:

BasicsModelGK3000-CS0220G
Capacity30 hp (22 kW)
Shipping weight31 kg
Dimension555*310*260 mm
I/O FeatureRated current45 A
Input voltage1 phase 220~240V AC
Input frequency50Hz/ 60Hz
Output voltage (Optional)3 phase AC 380V/ 400V/ 415V/ 440V/ 460V (Note: 440V, 460V output voltage only for the 1-phase 240V input VFD)
Output frequency0.00~400.00Hz
Over load capacity150% of rated current for 1 minute, 180% of rated current for 3 seconds
Control FeatureControl modeV/F control;
Sensorless vector control;
CommunicationRS485
Speed regulation1:100
Start torque150% of rating torque at 1 Hz
Speed control accuracy≤±0.5% of rating synchronous speed
Frequency precisionDigital setting: max frequency x± 0.01%;
Analog setting: max frequency x± 0.2%
Frequency resolutionAnalog setting: 0.1% of max frequency;
Digital setting: 0.01Hz
Torque boostAutomatic torque boost, manual torque boost 0.1%~30.0%
Interior PID controllerBe convenient to make closed-loop system
Automatic energy save runningOptimize V/F curve automatically based on the load to realize power save running
Automatic voltage regulation (AVR)Can keep constant output voltage when power source voltage varies.
Automatic current limitingLimit running current automatically to avoid frequent over-current which will cause trip
EnvironmentEnclosure ratingIP 20
Temperature–10℃~ +40℃; VFD will be derated if ambient temperature exceed 40℃; each rise 1℃, the derate will be 5%
Humidity5%-95%, without condensation
Altitude≤1000m; VFD will be derated if above 1000m
Impingement and oscillationNormal running:<5.9m/s2 (0.6g); Transportation:<15m/s2 (1.5g)
Store environment–20℃~ +60℃; no dust, no corrosive gas, no direct sunlight

Tips: Variable frequency drive control mode

Vector control
Vector control is to control the size and phase of the stator current of the motor through the vector coordinate circuit, so as to control the excitation current and torque current of the motor in the d, q, 0 coordinate axis system respectively, and then achieve the purpose of controlling the motor torque. By controlling the action sequence and time of each vector and the action time of the zero vector, various PWM waves can be formed to achieve various control purposes. At present, the vector control methods actually used in the VFD mainly include the vector control method based on slip frequency control and the vector control method without speed sensor.

V/F control
V/F control is in order to obtain the ideal torque-speed characteristic, based on the idea that while changing the power frequency for speed regulation, it is proposed to keep the magnetic flux of the motor constant. Basically, general-purpose VFD use this control method. The V/F control inverter is very simple, but this method cannot achieve higher control performance. Moreover, at low frequencies, torque compensation must be performed to change the low-frequency torque characteristics.