Product Description |
Standard Certifications | IEC60947-2/C8201-2-1 |
Item No. | EZC250 |
Number of poles | 3,4 |
Electrical characteristics as per IEC60947-2 and EN60947-2 |
Rated current(A) | In | 100,125,150,160,175,200,225,250 |
Rated Operating Voltage(V) | Ue | 440v |
Rated Insulated Voltage (Ui) | Ui | 690v |
Rated impulse withstand voltage(kV) | Uimp | 6kV |
Types of Circuit Breakers |
| F | N | H |
Ultimate breaking capacity (kA rms Icu) | 220/230V | 25 | 50 | 85 |
380/400V | 18 | 25 | 36 |
415V | 18 | 25 | 36 |
440V | 15 | 20 | 25 |
550V | 5 | 8 | 10 |
Rated service breaking capacity (kA rms Icu) | 220/230V | 12.5 | 25 | 42.5 |
380/400V | 9 | 12.5 | 18 |
415V | 9 | 12.5 | 18 |
440V | 7.5 | 10 | 12.5 |
500V | 2.5 | 4 | 5 |
Utilization category |
| A |
Mechanical Parameters | Mechanical | 10000 |
Electrical | 5000 |
Protection |
Overload protection | Bimetal | ○ |
Instantaneous protection | Magnetic | ○ |
Auxiliaries |
Indication contacts | AX | ○ |
AL | ○ |
AXAL | ○ |
Voltage releases | SHT | ○ |
UVR | ○ |
Control | Manual | with toggle with direct or extended rotary handle |
Dimensions(mm) | 3P | 165X105X85.5 |
4P | 165X140X85.5 |