CCHN is a trusted U.S. registered company in industrial automation & controls, CCHN's goal is helping saving your money by bypassing all kinds of local dealers/agents in buying industrial automation products from Chinese manufacturers directly. You will be enjoyed to get free tech support on how to choose, how to wire, how to commissioning with CCHN professional engineers. Shopping for your automation systems on CCHN one-stop online store now. The price on the website only for sample reference. for Mass order,please send the enquiry to us.

Blog

Foam cutting is a device for processing materials in the chemical industry such as foam and sponges. It mainly uses the high

...
CCHN Industry
 
Close
Shopping Categories
Search

CCHN Industry

CCHN is a trusted U.S. registered company in industrial automation & controls, CCHN's goal is helping saving your money by bypassing all kinds of local dealers/agents in buying industrial automation products from Chinese manufacturers directly. You will be enjoyed to get free tech support on how to choose, how to wire, how to commissioning with CCHN professional engineers. Shopping for your automation systems on CCHN one-stop online store now. The price on the website only for sample reference. for Mass order,please send the enquiry to us.

Blog

Foam cutting is a device for processing materials in the chemical industry such as foam and sponges. It mainly uses the high

...
300 hp (220 kW) Soft starter, 440 A, 3ph 240v/415v/480v
 
Close
Shopping Categories
Search

300 hp (220 kW) Soft starter, 440 A, 3ph 240v/415v/480v


$1579.36
Inexpensive 300 hp soft starter, 220 kW three phase 240v, 415v, 480v, 690v soft starter, control AC induction motor in soft s
SKU: GS-220
Free Shipping Worldwide
Delivery date: 6-12 days

300 hp motor soft starter, 220 kW three phase 240v, 415v, 480v, 690v AC motor starter, manufacturer direct sale.

ModelGS2-220 (220v, 240v), GS3-220 (380v, 400v, 415v), GS4-220 (460v, 480v), GS6-220 (575v, 690v).
Capacity300 hp (220 kw)
Current440 amps at 380v/480v, 900 amps at 220v, 270 amps at 690v
Weight21 kgs
Dimension525*257*194 mm
InputVoltageThree-phase 240v, 400v, 480v, 690v AC
Frequency50Hz/ 60Hz
Adaptive MotorSquirrel-cage three-phase asynchronous motor
Starting TimesIt is recommended not to exceed 20 times per hour.
485 CommunicationDB9 interface, male plug, ① is RS485+, ⑥ is RS485-
Control Mode
  1. Operation panel control.
  2. Operation panel + external control.
  3. External control.
  4. External control + COM control.
  5. Operation panel + external + COM control.
  6. Operation panel + COM control.
  7. COM control.
  8. No start or stop operation.
Start Mode
  1. Current-limiting to start.
  2. Voltage ramp to start.
  3. Torque control + current-limiting to start.
  4. Torque control + voltage ramp to start.
  5. Current ramp to start.
  6. Voltage current-limiting double closed-loop start.
Stop Mode
  1. Soft stop.
  2. Free stop.
Protective Function
  1. Open loop protection for external instantaneous stop terminals.
  2. Over-heat protection for soft starter.
  3. Protection for too long starting time.
  4. Input open phase protection.
  5. Output open phase protection.
  6. Unbalanced three-phase protection.
  7. Starting over current protection.
  8. Running overload protection.
  9. Under voltage protection for power voltage.
  10. Overvoltage protection for power voltage.
  11. Protection for fault parameter setting of the soft starter.
  12. Load short circuit protection.
  13. Auto restart or incorrect wiring protection.
  14. Incorrect wiring protection of external control stop terminals.
AmbientPlace to be usedIndoor location with good ventilation free from corrosive gas and conductive dust.
AltitudeBelow 1000M. It has to increase the soft starter rate power when the altitude is more than 1000M.
Temperature-30 +55 oC
Humidity90%RH without dew condensation.
Vibration<0.5G
StructureEnclosureIP 20
CoolingNatural wind cooling.

Tips: Notice for soft starter

  1. The installation and maintenance of the soft starter shall be carried out by qualified professional.
  2. Do not use high-voltage test equipment (such as megger) to test the insulation of soft starter.
  3. If the motor is required to run reversibly, an inverting contactor can be installed on the incoming line side. Be careful not to install it on the output side of soft starter.
  4. The coil-type motor rotor can be winded with appropriate starter resistance to improve the starting torque, the soft starter can also be used to start the coil-type motor. When the motor reaches the top speed and keeps stable, starting resistance shall be bypassed to reduce power loss.
  5. It is strictly forbidden to place the power factor compensation capacitor on the output side of the soft starter and the capacitor cannot be switched during start-up.