ATO 1 pole 63 amp MCB miniature circuit breaker is an electrical switch to turn off the electrical circuit during a faulty condition to protect conductors.
Circuit Breaker Information
- Rated Current: 63 amp
- Rated Voltage: 230/400V AC, 50Hz
- Number of poles: 1 pole
- 6 kA short circuit interrupting capacity
- Accordance with IEC standard
- C curve trip characteristic gives you the ability to configure the exact protection scheme you required
Technical Data
Model | CHN-NB8-631PC63 |
Electrical Parameters | Height | 86 mm |
Width | 18 mm per pole |
Mounting | DIN Rail |
Rated Current (In) | 63A |
Number of poles | 1P |
Rated Voltage (Ue) | 230/400V |
Rated Insulation Voltage (Ui) | 500V |
Dielectric Test Voltage | 2000V |
Reted Frequency | 50Hz |
Short Circuit Interrupting Capacity | 6KA |
Trip Characteristic | C Curve (5-10In) |
Rated Short-Circuit Breaking Capacity | 6000A |
Operating Short-Circuit Breaking Capacity | 6000A |
Mechanical Parameters | Electrical Life | 10000 times |
Mechanical Life | 20000 times |
Flame Retardant Grade | V0 |
Protection Degree | Direct installation: IP20B Installed in the distribution box: IP40B |
Calibration Temperature | 30℃ |
Operating Temperature | -35℃~+70℃ |
Storage Temperature | -35℃~+85℃ |
Tightening Torque | 2 N.m |
Max. Tolerable Torque | 2.5 N.m |
Terminal Size Acceptability–Min/Max | 1 mm2 / 25mm2 |
Wire Insertion Depth | 13mm |
Circuit Breaker Dimension (Unit: mm)

Tips: Overload protection of miniature circuit breaker
The overload protection function of the miniature circuit breaker is based on the principle that the bimetal is oriented and bent regularly as the temperature rises. After the miniature circuit breaker is closed, in the normal working state, the internal bimetallic sheet generates heat due to a certain current passing through it. The two pieces of metal have different coefficients of thermal expansion and cause bending. The bending angle of the normal current (1.13In) is not large, so the thrust is not enough to trip the tripping mechanism. When the line is generally overloaded and the overload current (1.45In) is reached, the large bending angle of the bimetal touches the lever in the tripping mechanism, and the thrust is sufficient to push the tripping mechanism, so that the miniature circuit breaker trips and plays a role of overload protection. The magnitude of the current flowing through the MCB is different, and the degree of bending of the bimetallic sheet is also different. When the circuit is generally overloaded, the tripping time of the circuit breaker is generally longer because the overload current is not too large. The standard trip current is 1.45 times the rated current. The trip time should be within 1 hour.
Use a miniature circuit breaker in a low voltage electrical network. Low cost MCB with 63 amp current rating, used in AC 50Hz, 230/400V with a 6 kA short circuit withstand rating, is more sensitive to overcurrent and a reliable way to protect conductors.