Factory price miniature circuit breaker (MCB) is an electrical Switch which automatically switches off the electrical circuit during an abnormal condition of the network means in overload condition as well as faulty condition.
Circuit Breaker Information
- Rated Current: 32 amp
- Rated Voltage: 230/400V AC, 50Hz
- Number of poles: 1 pole
- 6 kA short circuit interrupting capacity
- Accordance with IEC standard
- C curve trip characteristic gives you the ability to configure the exact protection scheme you required
Technical Data
Model | CHN-NB8-631PC32 |
Electrical Parameters | Height | 86 mm |
Width | 18 mm per pole |
Mounting | DIN Rail |
Rated Current (In) | 32A |
Number of poles | 1P |
Rated Voltage (Ue) | 230/400V |
Rated Insulation Voltage (Ui) | 500V |
Dielectric Test Voltage | 2000V |
Reted Frequency | 50Hz |
Short Circuit Interrupting Capacity | 6KA |
Trip Characteristic | C Curve (5-10In) |
Rated Short-Circuit Breaking Capacity | 6000A |
Operating Short-Circuit Breaking Capacity | 6000A |
Mechanical Parameters | Electrical Life | 10000 times |
Mechanical Life | 20000 times |
Flame Retardant Grade | V0 |
Protection Degree | Direct installation: IP20B Installed in the distribution box: IP40B |
Calibration Temperature | 30℃ |
Operating Temperature | -35℃~+70℃ |
Storage Temperature | -35℃~+85℃ |
Tightening Torque | 2 N.m |
Max. Tolerable Torque | 2.5 N.m |
Terminal Size Acceptability–Min/Max | 1 mm2 / 25mm2 |
Wire Insertion Depth | 13mm |
Circuit Breaker Dimension (Unit: mm)

Tips for using miniature circuit breaker
Miniature circuit breaker is mainly used for circuit overload, short circuit, over current, loss of voltage, under voltage, grounding, leakage, dual power automatic switching and protection and operation of the motor during infrequent starting. The selection principle is in addition to complying with low-voltage electrical appliances.
- The rated voltage of the miniature circuit breaker should not be less than the rated voltage of the circuit.
- The rated current of the miniature circuit breaker and the rated current of the overcurrent release are not less than the calculated current of the circuit.
- The rated short-circuit breaking capacity of the miniature circuit breaker is not less than the maximum short-circuit current in the circuit.
- When selecting a type of distribution circuit breaker, it is necessary to consider the coordination between short-delay short-circuit making and breaking capacity and time-delay protection levels.
- The rated voltage of the miniature circuit breaker undervoltage release is equal to the rated voltage of the circuit.
- When it is used for motor protection, the starting current of the motor should be considered when selecting the circuit breaker and it will not operate during the starting time.
- The selection of miniature circuit breaker should also consider the selective coordination of circuit breaker and circuit breaker, circuit breaker and fuse.
ATO 1 pole 1A MCB miniature circuit breaker is an electrical switch to turn off the electrical circuit during a faulty condition to protect conductors, with 32 amp current rating, used in AC 50Hz, 230/400V with a 6 kA short circuit withstand rating.