Circuit Breaker Information
- Rated Current: 40 amp
- Rated Voltage: 230/400V AC, 50Hz
- Number of poles: 3 pole
- 6 kA short circuit interrupting capacity
- 35mm DIN rail mounted
- It can be manually switched ON and OFF as similar to normal switch if necessary
- Thermal-magnetic overcurrent protection, short circuit protection, with C curve trip characteristic
Technical Data
Model | CHN-NB8-633PC40 |
Electrical Parameters | Height | 86 mm |
Width | 18 mm per pole |
Mounting | DIN Rail |
Rated Current (In) | 40A |
Number of poles | 3P |
Rated Voltage (Ue) | 230/400V |
Rated Insulation Voltage (Ui) | 500V |
Dielectric Test Voltage | 2000V |
Reted Frequency | 50Hz |
Short Circuit Interrupting Capacity | 6KA |
Trip Characteristic | C Curve (5-10In) |
Rated Short-Circuit Breaking Capacity | 6000A |
Operating Short-Circuit Breaking Capacity | 6000A |
Mechanical Parameters | Electrical Life | 10000 times |
Mechanical Life | 20000 times |
Flame Retardant Grade | V0 |
Protection Degree | Direct installation: IP20B Installed in the distribution box: IP40B |
Calibration Temperature | 30℃ |
Operating Temperature | -35℃~+70℃ |
Storage Temperature | -35℃~+85℃ |
Tightening Torque | 2 N.m |
Max. Tolerable Torque | 2.5 N.m |
Terminal Size Acceptability–Min/Max | 1 mm2 / 25mm2 |
Wire Insertion Depth | 13mm |
Circuit Breaker Dimension (Unit: mm)

Tips: How to select a miniature circuit breaker
- Determine the number of poles of the miniature circuit breaker according to the number of lines to be protected. For example, the general household electricity is single-phase electricity, and the circuit consists of a neutral wire and a live wire. If both lines need to be protected, select two poles. If the neutral line does not need to be protected, choose a single pole.
- Determine the amperage of the mini circuit breaker according to the line load. For example, if the load capacity of the line is 20A and the rated working current of the electrical appliance is 10A, the circuit breaker selection should be> 10A, <20A.
- Determine the type of instantaneous protection according to the resistance type of electrical appliances in the loop. There are three types of instantaneous protection, and the corresponding current protection multiples are B: 3~5In, C: 5~10In, D10~14In (In is the rated current). If it's just an incandescent lamp, you can choose type B. Choose type C for general electricity use, and type D for air conditioning protection.
Economical price 3 pole 40 amp DIN rail mountable miniature circuit breaker is rated at 230/400V AC supply with 6kA short circuit breaking capacity. Short-circuit protection and overload protection, with C curve trip characteristic, DIN rail mounted.