20 amp 3 pole Miniature Circuit Breaker


$71.39
Three pole DIN rail mountable miniature circuit breaker is rated at 230/400V AC supply with 6kA short circuit breaking capaci
SKU: CHN-MCB-3P20
Free Shipping Worldwide
Delivery date: 6-12 days

Circuit Breaker Information

  • Rated Current: 20 amp
  • Rated Voltage: 230/400V AC, 50Hz
  • Number of poles: 3 pole
  • 6 kA short circuit interrupting capacity
  • 35mm DIN rail mounted
  • It can be manually switched ON and OFF as similar to normal switch if necessary
  • Thermal-magnetic overcurrent protection, short circuit protection, with C curve trip characteristic

Technical Data

ModelCHN-NB8-633PC20
Electrical ParametersHeight86 mm
Width18 mm per pole
MountingDIN Rail
Rated Current (In)20A
Number of poles3P
Rated Voltage (Ue)230/400V
Rated Insulation Voltage (Ui)500V
Dielectric Test Voltage2000V
Reted Frequency50Hz
Short Circuit Interrupting Capacity6KA
Trip CharacteristicC Curve (5-10In)
Rated Short-Circuit Breaking Capacity6000A
Operating Short-Circuit Breaking Capacity6000A
Mechanical ParametersElectrical Life10000 times
Mechanical Life20000 times
Flame Retardant GradeV0
Protection DegreeDirect installation: IP20B
Installed in the distribution box: IP40B
Calibration Temperature30℃
Operating Temperature-35℃~+70℃
Storage Temperature-35℃~+85℃
Tightening Torque2 N.m
Max. Tolerable Torque2.5 N.m
Terminal Size Acceptability–Min/Max1 mm2 / 25mm2
Wire Insertion Depth13mm

Circuit Breaker Dimension (Unit: mm)

20 amp 3 pole Miniature Circuit Breaker Dimensions

Tips: Motor protection circuit breaker selection
There are two features for motor as follows: Firstly, starting current is several times of rated current. Secondly, it has certain overload capacity. In order to ensure motor operation is reliable, circuit breaker should be chosen in accordance with these two features of motor.
How to choose a motor protective circuit breaker?

  1. The long time delay action current setting value is determined by the rated current of motor.
  2. The returnable time of 6 times of long time delay action current setting value of circuit breaker is larger than the actual starting time of motor.
  3. Instantaneous action current setting value of circuit breaker: Cage motor should be 8 to 15 times as large as the rated current of releaser; winding motor should be 3 to 6 times as large as the rated current of releaser.