Miniature circuit breaker is ideal for the protection of circuits in industrial, commercial, and residential sectors, and ensures the following functions: Protection against short-circuit and overload currents, isolation, protection of persons against indirect contact.
Circuit Breaker Information
- Rated Current: 4A
- Rated Voltage: 230/400V AC, 50Hz
- Number of poles: 1 pole
- 6 kA short circuit breaking capacity
- Accordance with IEC standard
- Possibility for locking the toggle in ON or OFF position
- C curve trip characteristic gives you the ability to configure the exact protection scheme you required
Technical Data
Model | CHN-NB8-631PC04 |
Electrical Parameters | Height | 86 mm |
Width | 18 mm per pole |
Mounting | DIN Rail |
Rated Current (In) | 4A |
Number of poles | 1P |
Rated Voltage (Ue) | 230/400V |
Rated Insulation Voltage (Ui) | 500V |
Dielectric Test Voltage | 2000V |
Reted Frequency | 50Hz |
Short Circuit Interrupting Capacity | 6KA |
Trip Characteristic | C Curve (5-10In) |
Rated Short-Circuit Breaking Capacity | 6000A |
Operating Short-Circuit Breaking Capacity | 6000A |
Mechanical Parameters | Electrical Life | 10000 times |
Mechanical Life | 20000 times |
Flame Retardant Grade | V0 |
Protection Degree | Direct installation: IP20B Installed in the distribution box: IP40B |
Calibration Temperature | 30℃ |
Operating Temperature | -35℃~+70℃ |
Storage Temperature | -35℃~+85℃ |
Tightening Torque | 2 N.m |
Max. Tolerable Torque | 2.5 N.m |
Terminal Size Acceptability–Min/Max | 1 mm2 / 25mm2 |
Wire Insertion Depth | 13mm
|
Circuit Breaker Dimension (Unit: mm)

Tips: Circuit breaker maintenance
Circuit breaker should be maintained to prevent from failure and leakage.
- Keep circuit breaker clean and air dry in use. Otherwise it may cause the following consequences: The insulation caused by the broken main contact makes the voltaic arc re-ignite and even generates the burst of arc extinguish chamber. The dielectric strength of supported porcelain bottle and arc extinguishing chamber is reduced, resulting in discharging. patent leather, rust and others may block the gas port, leading to the malfunction of main contact and congestion. If foreign bodies enter into the arc extinguishing chamber, it may bring about the burning of non-linear resistance due to long-term electricity caused by poor contact of main contact, even the burst of non-linear resistance porcelain bottle.
- Change the rubber parts regularly. The main circuit breaker is a pneumatic and electrical device with complicated structure. The rubber parts should be regularly replaced because components of main circuit breaker have high standard for sealing performance.
- Check main components regularly. The main components should be regularly checked to maintain a good technical condition.
- Clear carbide or metal particles inside the arc cover. If the arc cover is broken, it should be replaced. If there are small metal particles on the surface of main contact, they should be removed by gently wiping, rather than grinding.
- In the process of switching on and off, the movable parts and the parts of arc extinguish chamber work smoothly without blocking. If specific noise occurs from the iron core, the core surface should be cleaned up and the transmission mechanism should be injected with lubricating oil.
4 amp miniature circuit breaker with standard ratings of 6kA short circuit interrupting capacity at 230/400V AC single voltage, standard 35 mm DIN rail mounting. The mcb circuit breaker has c curve trip characteristic to suit most applications.