Miniature circuit breaker is ideal for the protection of circuits in industrial, commercial, and residential sectors, and ensures the following functions: Protection against short-circuit and overload currents, isolation, protection of persons against indirect contact.
Circuit Breaker Information
- Rated Current: 2A
- Rated Voltage: 230/400V AC, 50Hz
- Number of poles: 3 pole
- 6 kA short circuit breaking capacity
- IEC standard certified and marked
- Possibility for locking the toggle in ON or OFF position
Technical Data
Model | CHN-NB8-633PC02 |
Electrical Parameters | Height | 86 mm |
Width | 18 mm per pole |
Mounting | DIN Rail |
Rated Current (In) | 2A |
Number of poles | 3P |
Rated Voltage (Ue) | 230/400V |
Rated Insulation Voltage (Ui) | 500V |
Dielectric Test Voltage | 2000V |
Reted Frequency | 50Hz |
Short Circuit Interrupting Capacity | 6KA |
Trip Characteristic | C Curve (5-10In) |
Rated Short-Circuit Breaking Capacity | 6000A |
Operating Short-Circuit Breaking Capacity | 6000A |
Mechanical Parameters | Electrical Life | 10000 times |
Mechanical Life | 20000 times |
Flame Retardant Grade | V0 |
Protection Degree | Direct installation: IP20B Installed in the distribution box: IP40B |
Calibration Temperature | 30℃ |
Operating Temperature | -35℃~+70℃ |
Storage Temperature | -35℃~+85℃ |
Tightening Torque | 2 N.m |
Max. Tolerable Torque | 2.5 N.m |
Terminal Size Acceptability–Min/Max | 1 mm2 / 25mm2 |
Wire Insertion Depth | 13mm |
Circuit Breaker Dimension (Unit: mm)

Tips: Circuit breaker selection principle
- Circuit breakers' type and protection form, selected frame, device or current limiting should be determined in accordance with circuit protection requirements.
- The rated voltage of circuit breaker should be equal to or larger than the one of circuit protected.
- The rated voltage of under-voltage releaser of circuit breaker should be equal to the rated one of circuit protected.
- The rated current of circuit breaker and over-current releaser should be equal or larger than the calculated current of circuit protected.
- The ultimate breaking capacity of circuit breaker should be larger than the effective value of maximum short-circuit current.
- The protection feature of upstream and downstream circuit breaker in the distribution line should be coordinated with each other. The protection feature of downstream should be below the upstream, which is not intersecting.
- The long-time delay tripping current of circuit breaker should be less than the continuous current of wire.
Three pole thermal-magnetic miniature circuit breaker (MCB) in accordance with IEC standard for 35 mm DIN rail mounting with toggle actuation and 6kA interrupt capacity. C curve trip characteristic, give you the ability to configure the exact protection scheme you required.