Circuit Breaker Information
- Rated Current: 1 amp
- Rated Voltage: 230/400V AC, 50Hz
- Number of poles: 1 pole
- 6 kA short circuit interrupting capacity
- Accordance with IEC standard
- C curve trip characteristic gives you the ability to configure the exact protection scheme you required
Technical Data
Model | CHN-NB8-631PC01 |
Electrical Parameters | Height | 86 mm |
Width | 18 mm per pole |
Mounting | DIN Rail |
Rated Current (In) | 1A |
Number of poles | 1P |
Rated Voltage (Ue) | 230/400V |
Rated Insulation Voltage (Ui) | 500V |
Dielectric Test Voltage | 2000V |
Reted Frequency | 50Hz |
Short Circuit Interrupting Capacity | 6KA |
Trip Characteristic | C Curve (5-10In) |
Rated Short-Circuit Breaking Capacity | 6000A |
Operating Short-Circuit Breaking Capacity | 6000A |
Mechanical Parameters | Electrical Life | 10000 times |
Mechanical Life | 20000 times |
Flame Retardant Grade | V0 |
Protection Degree | Direct installation: IP20B Installed in the distribution box: IP40B |
Calibration Temperature | 30℃ |
Operating Temperature | -35℃~+70℃ |
Storage Temperature | -35℃~+85℃ |
Tightening Torque | 2 N.m |
Max. Tolerable Torque | 2.5 N.m |
Terminal Size Acceptability–Min/Max | 1 mm2 / 25mm2 |
Wire Insertion Depth | 13mm |
Circuit Breaker Dimension (Unit: mm)

Tips: Circuit breaker working principle
The main contacts of low voltage circuit breaker are operated manually or electrically. After the main contact is closed, it will be locked by the free tripping mechanism. The trip coil of over-current and the thermal element of thermal overload releaser are connected in series with the main circuit. The under-voltage releaser coil and the power supply are connected in parallel.
- When the circuit is short-circuited or severely over-loaded, the armature of over-current releaser will be pulled in to make the main contact cut off the main circuit under the effect of the free tripping mechanism.
- When the circuit is overloaded, the thermal elements of thermal releaser will bend the bimetal plates by heating to cut off the main circuit under the effect of the free tripping mechanism.
- When the circuit is in the state of under-voltage, the armature of under-voltage releaser will be released to cut off the main circuit under the effect of the free tripping mechanism.
- When the shunt trip is pressed, its armature will be pulled to cut off the main circuit under the effect of the free tripping mechanism.
1 pole miniature circuit breaker with 1A current rating, and can safely be used in AC 50Hz, 230/400V with a 6 kA short circuit withstand rating, provide overload and short circuit protection for conductors.