1 amp 1 pole Miniature Circuit Breaker


$57.49
1 pole miniature circuit breaker with 1A current rating, and can safely be used in AC 50Hz, 230/400V with a 6 kA short circui
SKU: CHN-MCB-1P01
Free Shipping Worldwide
Delivery date: 6-12 days

Circuit Breaker Information

  • Rated Current: 1 amp
  • Rated Voltage: 230/400V AC, 50Hz
  • Number of poles: 1 pole
  • 6 kA short circuit interrupting capacity
  • Accordance with IEC standard
  • C curve trip characteristic gives you the ability to configure the exact protection scheme you required

Technical Data

ModelCHN-NB8-631PC01
Electrical ParametersHeight86 mm
Width18 mm per pole
MountingDIN Rail
Rated Current (In)1A
Number of poles1P
Rated Voltage (Ue)230/400V
Rated Insulation Voltage (Ui)500V
Dielectric Test Voltage2000V
Reted Frequency50Hz
Short Circuit Interrupting Capacity6KA
Trip CharacteristicC Curve (5-10In)
Rated Short-Circuit Breaking Capacity6000A
Operating Short-Circuit Breaking Capacity6000A
Mechanical ParametersElectrical Life10000 times
Mechanical Life20000 times
Flame Retardant GradeV0
Protection DegreeDirect installation: IP20B
Installed in the distribution box: IP40B
Calibration Temperature30℃
Operating Temperature-35℃~+70℃
Storage Temperature-35℃~+85℃
Tightening Torque2 N.m
Max. Tolerable Torque2.5 N.m
Terminal Size Acceptability–Min/Max1 mm2 / 25mm2
Wire Insertion Depth13mm

Circuit Breaker Dimension (Unit: mm)

1 amp 1 pole Miniature Circuit Breaker Dimensions

Tips: Circuit breaker working principle
The main contacts of low voltage circuit breaker are operated manually or electrically. After the main contact is closed, it will be locked by the free tripping mechanism. The trip coil of over-current and the thermal element of thermal overload releaser are connected in series with the main circuit. The under-voltage releaser coil and the power supply are connected in parallel.

  1. When the circuit is short-circuited or severely over-loaded, the armature of over-current releaser will be pulled in to make the main contact cut off the main circuit under the effect of the free tripping mechanism.
  2. When the circuit is overloaded, the thermal elements of thermal releaser will bend the bimetal plates by heating to cut off the main circuit under the effect of the free tripping mechanism.
  3. When the circuit is in the state of under-voltage, the armature of under-voltage releaser will be released to cut off the main circuit under the effect of the free tripping mechanism.
  4. When the shunt trip is pressed, its armature will be pulled to cut off the main circuit under the effect of the free tripping mechanism.