15 kVA isolation transformer is an automation single phase distribution transformer, convert primary voltage 415V to secondary voltage 120V/240V. Work efficiency up to 95%, low energy consumption and high efficiency make split-phase transformers an ideal choice.
15 kVA Single Phase to Split Phase Transformer Specifications
Model | CHN-DGS15kVA |
Phase | Single phase to split phase |
Capacity | 15 kVA |
Primary Voltage | 1 Phase / 2 phase 110, 120, 208, 220, 230, 240, 380, 415, 440, 460, 480, |
Secondary Voltage | 120V/240V AC(L1, L2, N, L+L=240V, L+N=120V) |
Frequency | 50/60Hz |
Winding Material | Aluminum/Copper wire (Optional) |
Work Efficiency | ≥95% |
Insulation Resistance | ≥50 MΩ |
Electrical Strength | 2000V AC/1 min |
Noise | ≤35dB (1 meter) |
Insulation Grade | Grade B (130℃), Grade F (155℃), Grade H (180℃) |
Cooling Method | Natural or air cooling |
Overload Capacity | Allow more than 1.2 times rated load to work for up to 1 hour |
Induced Overvoltage Withstand Test | 125Hz/800V/min |
Transformation Ratio | <3% |
Air Carrying Current | <6% |
Impedance Voltage | About 6% |
Total Losses | 10% |
Certification | CE, ISO |
Temperature | -15℃~+45℃ |
Humidity | ≤90%RH, without condensation |
Altitude | <2000m, non corrosive gas and conductive dust |
Enclosure Protection Grade | IP20 |
Warranty | 12 months |
Weight of Aluminium Wire Transformer | Open type: 145kg Protected type: 180kg |
Weight of Copper Wire Transformer | Open type: 150kg Protected type: 185kg |
15 kVA Single Phase to Split Phase Transformer Schematic Diagram

15 kVA Single Phase to Split Transformer Dimension (Unit: mm)

Aluminium Wire Transformer Size | Copper Wire Transformer Size |
Open type: a*b*c=370*350*520mm | Open type: a*b*c=300*330*370mm |
Mouting size: D*E=190*190mm (aperture: 20*10mm) | Mouting size: 220*220mm (aperture: 20*10mm) |
Protected type: A*B*C=420*610*610mm | Protected type: A*B*C=420*610*610mm |
Tips: What is transformer load operation?
The load operation of the transformer refers to the working condition when the original winding is connected to the power supply voltage and the auxiliary winding is connected to the load. At this time, the secondary side of the transformer also has current flowing, and the access circuit of the original transformer increases correspondingly compared with no-load, and the secondary side voltage will be affected by the load and change.
15kVA single phase to split phase distribution transformer step down 415V input voltage to 120V/240V output voltage, frequency 50/60Hz, winding material can choose aluminum or copper wire. Overload Capacity allows working at 1.2 times the rated load for up to 1 hour, making the single-phase transformer safe and reliable.