CCHN is a trusted U.S. registered company in industrial automation & controls, CCHN's goal is helping saving your money by bypassing all kinds of local dealers/agents in buying industrial automation products from Chinese manufacturers directly. You will be enjoyed to get free tech support on how to choose, how to wire, how to commissioning with CCHN professional engineers. Shopping for your automation systems on CCHN one-stop online store now. The price on the website only for sample reference. for Mass order,please send the enquiry to us.

Blog

Foam cutting is a device for processing materials in the chemical industry such as foam and sponges. It mainly uses the high

...
CCHN Industry
 
Close
Shopping Categories
Search

CCHN Industry

CCHN is a trusted U.S. registered company in industrial automation & controls, CCHN's goal is helping saving your money by bypassing all kinds of local dealers/agents in buying industrial automation products from Chinese manufacturers directly. You will be enjoyed to get free tech support on how to choose, how to wire, how to commissioning with CCHN professional engineers. Shopping for your automation systems on CCHN one-stop online store now. The price on the website only for sample reference. for Mass order,please send the enquiry to us.

Blog

Foam cutting is a device for processing materials in the chemical industry such as foam and sponges. It mainly uses the high

...
6000VA Control Transformer, 220/440V to 120/48/12V
 
Close
Shopping Categories
Search

6000VA Control Transformer, 220/440V to 120/48/12V


$1366.92
Cheap price 6kVA single phase control transformer applicable to 50/60Hz, step down 220/440V primary voltage to 120/48/12V thr
SKU: CHN-T-BK6000VA
Free Shipping Worldwide
Delivery date: 6-12 days

High efficiency control transformer is applicable for AC 50/60Hz, fully electric isolation between primary side and secondary sides, is designed to convert 220/440V input voltage to 120/48/12V three sets of output voltages.

Specifications

Product NameSingle phase control transformer 
Product ModelATOBK-6000VA
Winding MaterialEnameled copper wire or enameled aluminum wire
Capacity6000 VA
Primary Voltage (VAC)110, 120, 208, 220, 230, 240, 380, 400, 480, 110/220, 120/240, 220/440, 240/480, 220/380/480V, 440/460/480V...(Customized)
Secondary Voltage (VAC)6, 12, 24, 36, 48, 110/48, 120/24, 208/36, 220/48, 230/36, 240/120, 120/48/12, 110/36/24, 127/36/6, 208/48/36/24...(Customized)
Frequency50 / 60Hz
Insulation LevelF / H
Withstand Voltage TestPrimary to secondary 2.5KV/min
Primary to safety ground 2.5KV/min
Secondary to safety ground 1.5KV/min
Insulation ResistancePrimary to secondary 2500V>100 megohm
Primary to safety ground 2500V>100 megohm
Secondary to safety ground 1500V>100 megohm
Induction Withstand Voltage Test125Hz/ 800V/min
Ground Resistance25<A80 milliohm
Cooling MethodNatural or air cooling
Transformation Ratio<3%
Air Carrying Current<6%
Impedance Voltageabout 6%
Total Losses0.1
Efficiency80%~99%
Operating Temperature-25℃~40℃ (40℃, 93% RH, 56 days)
Storage Temperature-25℃~100℃ (40℃, 93% RH, 56 days)
CertificateCE, ISO
Warranty12 months
SizeOverall size: 240*190*230mm, Hold distance for installation: 180*170mm, Installation hold: 20*10mm
Weight55kg

Schematic diagram illustration

Control transformer schematic diagram illustration

 Control transformer dimension

Control transformer dimension

Overall size (mm)Hole distance for installation (mm)Installation hole
(mm) K x J
BEDAC
24019023018017020 x 10

Tips: How to improve the service life of control ransformer?

We know that when using the control transformer, we should pay attention to two points: one is the power of the transformer, the other is the correct wiring. The total power of the load connected to the secondary side shall not be greater than the power of the control transformer, and short circuit is not allowed. Otherwise, the temperature will be too high, and it will be burned if it is serious. The main parameters of the transformer are voltage ratio, voltage regulation rate, copper resistance, efficiency, temperature rise and electrical strength. Different types of transformers have some special requirements. The transformer shall have a long enough life. The main factor that determines the service life of low-voltage transformer is thermal aging. Because the insulation system works in high temperature for a long time, the evaporation of paint film makes the insulation material embrittlement and crack, resulting in electric shock. When the working temperature increases by 8-10 ℃, the service life will be shortened by half.

For high-voltage transformer, corona discharge is the main factor affecting the service life. The influence is related to working frequency, corona discharge intensity, corona resistance of insulating materials and working electric field intensity. Therefore, corona discharge should be avoided. Under various environmental conditions, the most important factor affecting the reliable operation of transformer is humidity. When the transformer is exposed to damp and hot environment for a long time, its insulation resistance will drop seriously, even the insulation layer will break down and burn down. Here, ATO reminds you that effective moisture-proof measures must be taken for the transformers used in the more important radio products and electronic instruments. In case of rainy season, it is necessary to turn on the electricity regularly to remove the moisture, so as to improve the service life of the control transformer.