150 hp VFD, 110 kW three phase 230V, 400V, 480V variable frequency drive with good performance.
Specification:
Basics | Model | GK3000-4T1100G/ GK3000-2T1100G |
Capacity | 150 hp (110 kW) |
Shipping weight | 51 kg |
Dimension | 650*400*300 mm |
I/O Feature | Rated current | 210 A |
Input voltage | 3 phase 230V /400V /480V AC ±15% (Optional) |
Input frequency | 50Hz/ 60Hz |
Output voltage | 3 phase AC 0~input voltage |
Output frequency | 0.00~400.00Hz |
Over load capacity | 150 % of rated current for 1 minute, 180 % of rated current for 3 seconds |
Control Feature | Control mode | V/F control; Sensorless vector control; |
Communication | RS485 |
Speed regulation | 1:100 |
Start torque | 150% of rating torque at 1 Hz |
Speed control accuracy | ≤±0.5% of rating synchronous speed |
Frequency precision | Digital setting: max frequency x± 0.01%; Analog setting: max frequency x± 0.2% |
Frequency resolution | Analog setting: 0.1% of max frequency; Digital setting: 0.01Hz |
Torque boost | Automatic torque boost, manual torque boost 0.1%~30.0% |
Interior PID controller | Be convenient to make closed-loop system |
Automatic energy save running | Optimize V/F curve automatically based on the load to realize power save running |
Automatic voltage regulation (AVR) | Can keep constant output voltage when power source voltage varies. |
Automatic current limiting | Limit running current automatically to avoid frequent over-current which will cause trip |
Environment | Enclosure rating | IP 20 |
Temperature | –10℃~ +40℃; VFD will be derated if ambient temperature exceed 40℃; each rise 1℃, the derate will be 5% |
Humidity | 5%-95%, without condensation |
Altitude | ≤1000m; VFD will be derated if above 1000m |
Impingement and oscillation | Normal running:<5.9m/s2 (0.6g); Transportation:<15m/s2 (1.5g) |
Store environment | –20℃~ +60℃; no dust, no corrosive gas, no direct sunlight |
Tips: Variable frequency drive and upper computer debugging
After the no-load power-on test, with motor no-load test and on-load test, the manual basic settings of VFD have been completed, and VFD can be connected with the upper computer for further system debugging. Let the VFD control line directly connect with the upper computer control line, and change the operation mode to terminal control. According to the requirements of the upper computer system, set the VFD receive frequency signal terminal range to 0~5V or 0~10V, and set the sampling response speed of analog frequency signal. If additional monitor is required, select the analog output monitoring item and adjust the range of this monitoring item terminal.
Low price 150 hp (110 kW) VFD for energy savings, three phase 230V, 400V, 480V for selection, heavy duty vector control variable frequency drive direct sale by manufacturer.