125 hp heavy duty variable frequency drive, three phase 220V, 415V, 480V for selection, brand new direct sale by manufacturer.
Specification:
Basics | Model | GK3000-4T0900G/ GK3000-2T0900G |
Capacity | 125 hp (90 kW) |
Shipping weight | 51 kg |
Dimension | 650*400*300 mm |
I/O Feature | Rated current | 176 A |
Input voltage | 3 phase 220V /415V /480V AC ±15% (Optional) |
Input frequency | 50Hz/ 60Hz |
Output voltage | 3 phase AC 0~input voltage |
Output frequency | 0.00~400.00Hz |
Over load capacity | 150% of rated current for 1 minute, 180% of rated current for 3 seconds |
Control Feature | Control mode | V/F control; Sensorless vector control; |
Communication | RS485 |
Speed regulation | 1:100 |
Start torque | 150% of rating torque at 1 Hz |
Speed control accuracy | ≤±0.5% of rating synchronous speed |
Frequency precision | Digital setting: max frequency x± 0.01%; Analog setting: max frequency x± 0.2% |
Frequency resolution | Analog setting: 0.1% of max frequency; Digital setting: 0.01Hz |
Torque boost | Automatic torque boost, manual torque boost 0.1%~30.0% |
Interior PID controller | Be convenient to make closed-loop system |
Automatic energy save running | Optimize V/F curve automatically based on the load to realize power save running |
Automatic voltage regulation (AVR) | Can keep constant output voltage when power source voltage varies. |
Automatic current limiting | Limit running current automatically to avoid frequent over-current which will cause trip |
Environment | Enclosure rating | IP 20 |
Temperature | –10℃~ +40℃; VFD will be derated if ambient temperature exceed 40℃; each rise 1℃, the derate will be 5% |
Humidity | 5%-95%, without condensation |
Altitude | ≤1000m; VFD will be derated if above 1000m |
Impingement and oscillation | Normal running:<5.9m/s2 (0.6g); Transportation:<15m/s2 (1.5g) |
Store environment | –20℃~ +60℃; no dust, no corrosive gas, no direct sunlight |
Tips: Variable frequency drive loading debugging process
- Manually operate the stop button of the inverter panel to observe the stopping of the motor and the display window of the inverter to see if there is any abnormality.
- If the VFD has overcurrent protection during motor stopping, the acceleration deceleration time should be reset. If the overcurrent occurs during the start-up process, the acceleration time may be extended. If the overcurrent occurs during the braking process, the deceleration time should be extended.
- If the VFD is still protected in the limited time, change the stopping operating curve from straight to S-shaped, U-shaped or S-shaped, anti-U-shaped.
- If the VFD still has a running fault, try to increase the maximum current protection value, but cannot cancel the protection, and should leave at least 10% to 20% protection margin.
- If the Problem still cannot be solved, replace a higher power VFD.
- If the VFD drives the motor in the boot process does not reach the preset speed, there may be two cases:
(1) Electromechanical resonance occurs in the system, which can be judged from the sound of the motor. Depending on the frequency of the system, set the jump across and span on the VPf curve. When the motor is accelerating, it will automatically skip these frequency segments to ensure properly operation.
(2) If the motor torque output capacity is not enough, the manual torque lifting function can be set. The set value should not be too high, or the motor temperature will be increased. If it still have problem, should use VPf ratio constant method, or switch no-speed sensor space vector control method. For fan and pump loads, should reduce the curve values of the torque reduction.
Cheap price 125 hp (90 kW) VFD for induction motor speed controls, three phase 220V, 415V, 480V energy saving variable frequency drive, direct sale by manufacturer in wholesale price.