150 hp AC motor soft starter, 110 kW three phase 240v, 415v, 480v, 690v for choice.
Model | GS2-110 (220v, 240v), GS3-110 (380v, 400v, 415v), GS4-110 (460v, 480v), GS6-110 (575v, 690v). |
Capacity | 150 hp (110 kw) |
Current | 230 amps at 380v/480v, 470 amps at 220v |
Weight | 21 kgs |
Dimension | 525*257*194 mm |
Input | Voltage | Three-phase 230v, 400v, 460v, 660v AC |
Frequency | 50Hz/ 60Hz |
Adaptive Motor | Squirrel-cage three-phase asynchronous motor |
Starting Times | It is recommended not to exceed 20 times per hour. |
485 Communication | DB9 interface, male plug, ① is RS485+, ⑥ is RS485- |
Control Mode | - Operation panel control.
- Operation panel + external control.
- External control.
- External control + COM control.
- Operation panel + external + COM control.
- Operation panel + COM control.
- COM control.
- No start or stop operation.
|
Start Mode | - Current-limiting to start.
- Voltage ramp to start.
- Torque control + current-limiting to start.
- Torque control + voltage ramp to start.
- Current ramp to start.
- Voltage current-limiting double closed-loop start.
|
Stop Mode | - Soft stop.
- Free stop.
|
Protective Function | - Open loop protection for external instantaneous stop terminals.
- Over-heat protection for soft starter.
- Protection for too long starting time.
- Input open phase protection.
- Output open phase protection.
- Unbalanced three-phase protection.
- Starting over current protection.
- Running overload protection.
- Under voltage protection for power voltage.
- Overvoltage protection for power voltage.
- Protection for fault parameter setting of the soft starter.
- Load short circuit protection.
- Auto restart or incorrect wiring protection.
- Incorrect wiring protection of external control stop terminals.
|
Ambient | Place to be used | Indoor location with good ventilation free from corrosive gas and conductive dust. |
Altitude | Below 1000M. It has to increase the soft starter rate power when the altitude is more than 1000M. |
Temperature | -30 +55 oC |
Humidity | 90%RH without dew condensation. |
Vibration | <0.5G |
Structure | Enclosure | IP 20 |
Cooling | Natural wind cooling. |
Tips: Problems to be noticed for soft starter electrification debugging
Frequent starting of the soft starter is forbidden, because the frequent starting of the high current will burn the SCR. The required soft starting time is 10 to 20 times / h, and the time interval of the starting with loads is 3 ~ 6min.
After the start signal is issued, the motor stops immediately after slow turning and the line protector operates. Under this situation, the motor may stall, and it can be restarted after the motor stalling is eliminated.
After the start signal is issued, the motor starts, but the protection trip occurs shortly after the starting. This fault causes include that the parameter adjustment of the thermal protection of the motor is too small; motor number and design do not match; and the fan has air leak. It is necessary to start after the trouble shooting.
The motor cannot be started after the start signal is issued. There are many reasons for this situation, the main circuit and control circuit is not powered, the control wiring is wrong, and the motor has failure and so on.