Close
Shopping Categories
Search

CCHN Industry

CCHN is a trusted U.S. registered company in industrial automation & controls, CCHN's goal is helping saving your money by bypassing all kinds of local dealers/agents in buying industrial automation products from Chinese manufacturers directly. You will be enjoyed to get free tech support on how to choose, how to wire, how to commissioning with CCHN professional engineers. Shopping for your automation systems on CCHN one-stop online store now. The price on the website only for sample reference. for Mass order,please send the enquiry to us.

Blog

Foam cutting is a device for processing materials in the chemical industry such as foam and sponges. It mainly uses the high

...
CCHN Industry
 
Close
Shopping Categories
Search

CCHN Industry

CCHN is a trusted U.S. registered company in industrial automation & controls, CCHN's goal is helping saving your money by bypassing all kinds of local dealers/agents in buying industrial automation products from Chinese manufacturers directly. You will be enjoyed to get free tech support on how to choose, how to wire, how to commissioning with CCHN professional engineers. Shopping for your automation systems on CCHN one-stop online store now. The price on the website only for sample reference. for Mass order,please send the enquiry to us.

Blog

Foam cutting is a device for processing materials in the chemical industry such as foam and sponges. It mainly uses the high

...
50 hp (37 kW) Soft starter, 75 A, 3ph 240v/400v/480v
 
Close
Shopping Categories
Search

50 hp (37 kW) Soft starter, 75 A, 3ph 240v/400v/480v


$479.12
Inexpensive 50 hp soft starter, 37 kW three phase 240v, 400v, 480v for selection, make induction motor in soft start & so
SKU: GS-037
Free Shipping Worldwide
Delivery date: 6-12 days

50 hp soft starter, 37 kW three phase 240v, 400v, 480v, 690v AC motor starter for selection.

ModelGS2-037 (220v, 240v), GS3-037 (380v, 400v, 415v), GS4-037 (460v, 480v), GS6-037 (575v, 690v).
Capacity50 hp (37 kw)
Current75 amps at 380v/480v, 150 amps at 220v
Weight5 kgs
Dimension270*146*160 mm
InputVoltageThree-phase 230v, 380v, 460v, 690v AC
Frequency50Hz/ 60Hz
Adaptive MotorSquirrel-cage three-phase asynchronous motor
Starting TimesIt is recommended not to exceed 20 times per hour.
485 CommunicationDB9 interface, male plug, ① is RS485+, ⑥ is RS485-
Control Mode
  1. Operation panel control.
  2. Operation panel + external control.
  3. External control.
  4. External control + COM control.
  5. Operation panel + external + COM control.
  6. Operation panel + COM control.
  7. COM control.
  8. No start or stop operation.
Start Mode
  1. Current-limiting to start.
  2. Voltage ramp to start.
  3. Torque control + current-limiting to start.
  4. Torque control + voltage ramp to start.
  5. Current ramp to start.
  6. Voltage current-limiting double closed-loop start.
Stop Mode
  1. Soft stop.
  2. Free stop.
Protective Function
  1. Open loop protection for external instantaneous stop terminals.
  2. Over-heat protection for soft starter.
  3. Protection for too long starting time.
  4. Input open phase protection.
  5. Output open phase protection.
  6. Unbalanced three-phase protection.
  7. Starting over current protection.
  8. Running overload protection.
  9. Under voltage protection for power voltage.
  10. Overvoltage protection for power voltage.
  11. Protection for fault parameter setting of the soft starter.
  12. Load short circuit protection.
  13. Auto restart or incorrect wiring protection.
  14. Incorrect wiring protection of external control stop terminals.
AmbientPlace to be usedIndoor location with good ventilation free from corrosive gas and conductive dust.
AltitudeBelow 1000M. It has to increase the soft starter rate power when the altitude is more than 1000M.
Temperature-30 +55 oC
Humidity90%RH without dew condensation.
Vibration<0.5G
StructureEnclosureIP 20
CoolingNatural wind cooling.

Tips: Soft starter installation methods

  1. The soft starter should install indoors in accordance with the shell protection level (usually IP20) requirement.
  2. Should install vertically, in the top and bottom of the soft starter should leave space at least 200mm width to facilitate heat dissipation.
  3. If the control cabinet is equipped with thermal relay, should use segregation board to prevent cold or hot airflow blowing to the thermal relay, to avoid affecting the action value of the thermal relay.
  4. Carefully read the instructions to understand the function of each terminal, ensure correct wiring.
  5. Usually don't use megger test the phase and relative to the ground insulation resistance. If it is necessary, must let three-phase input and output short circuit, and unplug all the plugs on the control panel, and then testing.
  6. When the soft starter input connects to the power supply, the output will bring a high induction voltage when the load opens circuit or loss of phase. So when in installation, commission, maintenance and use, prohibit contacting the soft starter output terminal, so as not to causing electric shock accident.
  7. If soft starter connects compensation capacitors to improve the power factor, the capacitor must connect to the soft starter input terminal, not output terminal, otherwise it will cause damage to the soft starter.
  8. The soft starter input and output terminals can't be connected reversely, otherwise it may cause damage to the soft starter and motor.
  9. If the soft starter has bypass contactor, carefully wiring (connect the contactor main contact) , can't cause short-circuit accident.
  10. When measure the motor insulation resistance, must disconnect the three lines between soft starter before proceeding.