2 kVA solid state frequency converter (AC power supply), converting 60Hz to 50Hz, also changing 110V/120V to 220V/230V/240V, reliable power frequency changer with pure sine wave output.
Specification:
Model | HZ-50-1102 (Cabinet Type), HZ-60-1102 (Benchtop Type) |
Capacity | 2 kVA |
Dimension | Benchtop Design | 660*510*250mm |
Cabinet Design | 550*400*670mm |
Weight | Benchtop Design | 49 kg |
Cabinet Design | 60 kg |
Input | Voltage | 1 Phase 2 Wire: 110V, 120V, 220V, 230V, 240V ± 10% (Option *) |
Frequency | 50 Hz, 60 Hz or 400 Hz ± 5% |
Output | Voltage, current | 110V Setting (Low grade): 0-150V, 16.8A |
220V Setting 0-300V (High grade): 0-300V, 8.4A |
Load stabilization Rate | ≤±1% |
Frequency | 50Hz, 60Hz up to 400Hz adjustable Note: -When the output is 400Hz, the load capacity can only reach 50% of the rated capacity. -When the output is ≤120Hz, the load capacity can reach 100% of the rated value. -You can just adjust converter output frequency in the range (40-400Hz) for 400Hz option. |
Frequency Stability | ≤±0.01% |
Harmonic Distortion | Pure Sine Wave ≤2% |
Frequency meter | 4 digit, digital frequency meter, resolution 0.1Hz/Step |
Voltmeter | 4 digit, digital voltage meter, resolution 0.1V |
Ammeter | 4 digit, digital ammeter, resolution 0.1A |
Watt meter | 4 digit, digital Watt meter, resolution 0.1W |
Protection | With overload, short circuit, over temperature |
Instantaneous power failure protection and alarm device |
Working Environment | Temperature | 0 - 40 deg.℃ |
Humidity | 0 - 90% (Non condensation) |
Warranty | 18 months |
Tips: Can the Variable Frequency Drive be used as the Frequency Converter?
Question: Can the VFD be used as the AC Power supply?
Answer: No. Because in practical application, the main application of the VFD is for the speed regulation of the motor. Moreover, it can only be equipped with one motor. Therefore, the variable-speed drive can not be used as the frequency converter. In addition, the AC frequency converter is exclusively designed and manufactured for import and export equipment, converts a basic fixed-frequency, fixed voltage sine-wave power to a variable-frequency, variable-voltage output, conforms to the power supply system of Europe and America. Thus can be used as the power supply of the import electricity equipment and production line, or the test power source of the import and export electrical product.
2 kVA static frequency converter, 1 phase 110V/120 60Hz power to 220V/230V/240V 50Hz boost in one step (vice versa), voltage and Hertz converter with pure sine wave output for US and Europe home appliances.