Model | LW12000 |
Power | 12000 Watt |
Phase | Split phase |
AC Input | Input Voltage Waveform | sinusoidal (utility or generator) |
Nominal input Voltage | HOT1-HOT2: 240VAC |
Low Line Disconnect | 180Vac±4% (Normal) or 140Vac±4% (Wide) |
Low Line Re-connect | 190Vac±4% (Normal) or 150Vac±4% (Wide) |
High Line Disconnect | 270Vac±4% (Normal) or 270Vac±4% (Wide) |
High Line Re-connect | 260Vac±4% (Normal) or 260Vac±4% (Wide) |
Max AC input Voltage | Max280V |
Frequency | 50Hz:41-54Hz, 60Hz:51-64Hz |
AC Output | Output Voltage Waveform | Sinewave |
Power Factor | 1 |
Nominal Output Voltage (V) | HOT1-N: 120Vac ±10%rms; HOT2-N: 120Vac ±10%rms; HO1-HOT2: 240Vac ±10%rms |
output phase difference | HOT1-N and HOT2-N is 180°; HOT1-N and HOT1-HOT2 is 0°; HOT2-N and HOT1-HOT2 is 180° |
Nominal Output Frequency (Hz) | 50Hz ± 1Hz, 60Hz ± 1Hz |
AC Charger | Nominal Charger Current | 20A/35A/50A/70A/90A (According to the inverter model) ; adjustable 5 stages charging current |
Over charge Protection | Bat.V≥15.5VDC for 12V battery, Bat.V≥31.0VDC for 24V battery, Bat.V≥62.0VDC for 48V battery; beeps 0.5s every 1s & fault after 60s |
Solar charger | Rated Charge Current | alternative 40A/60A |
PV Input Voltage range | 15VDC-40VDC for 12VDC, 30VDC-75VDC for 24VDC, 60-145VDC for 48V |
Max.PV open circuit array Voltage | 12V for 40Vdc, 24V for 75Vdc, 48V for 145Vdc |
Charger mode | MPPT |
PV Low Voltage Re-connect | PV≥Bat.V+3V |
PV Low Voltage Disconnect | PV≦Bat.V |
Effificiency | ≥97% |
DC Input | Battery Voltage | 48VDC |
Low Battery Alarm | 42VDC±1.2VDC |
Low DC input shut & down | 40VDC±1.2VDC |
High DC input Alarm & Fault | 64VDC±1.2VDC |
Efficiency | Efficiency (Battery Mode) | ≥87% |
Efficiency (Line Mode) | >98% |
Transfer Time | AC to DC | 20ms (max) |
DC to AC | 15ms (max) |
System Parameter | Over-Load Protection | 110%<load<150%, beeps 0.5s every 1s, and Fault after 60s off the output, load>150%, beeps 0.5s every 1s, and Fault after 20s |
Output Short Circuit Protection | YES |
Surge Rating | 1:3 (VA) |
Protections | Low battery, over charging, over load, over temp |
Indicators | LED+LCD Display |
General Specifications | Operating Temperature Range | 0℃~40℃ |
Stor age Temperature | ﹣15℃~60℃ |
Operation humidity | 5% to 95% (non-condensing) |
Audible Noise | 80dB max |
cooling | Forced air, variable speed fan |
Dimension (L*W*H) | 627x416x204mm |
Net Weight (kg) | 79kg |