95A 4 pole AC contactor is used under 50Hz or 60Hz, as a bypass contactor, making or breaking electric ciucuits at a long distance, frequent starting, stopping and controlling AC motors.
Specifications
| Model | CJX2-95 |
| Rated Operational Current (AC-3) | 380V | 95A |
| 660V | 49A |
| Conventional Heating Current | 110A |
| Rated Insulation Voltage | 690V |
| Power of Controllable 3-phase Squirrel-cage Motor (AC-3) | 220V | 25kW |
| 380V | 45kW |
| 660V | 55kW |
| Operational Frequency (AC-3) | Electric Life | 600 times/h |
| Mechanical Life | 2400 times/h |
| Service Life | Electric Life (104 times) | 60 |
| Mechanical Life (104 times) | 600 |
| Matching Fusing Model | RT16-125 |
| Average Power Consumption (20℃) @ 50Hz | Pick-up | 230VA |
| Holding | 32VA |
| Unit weight(kg) | 4P (4N/O) | 1.59 |
| 4P (2N/O+2N/C) | 1.65 |
| Ambient Temperature | -5℃~+40℃ |
| Altittude | ≤2000m |
| Rail Size | 75mm |
| Class of Pollution | Class 3 |
| Installation Category | Ⅲ |
Dimensions (unit: mm)
4P (4NO) AC contactor

4P (2NO+2NC) AC contactor

Tips: The contact of AC contactor is overheating or burning for eight-hour working, how to solve?
Possible Causes:
- Contact spring pressure is too small
- There is oil on the contact, or the surface is uneven, and the metal particles are prominent.
- The ambient temperature is too high or used in a closed control box
- Copper contacts for long-term work
- The overtravel of the contact is too small
Processing method:
- Increase the contact spring pressure
- Clean the contact surface
- Contactor derating
- Adjust the contact overtravel or replace the contact