CCHN is a trusted U.S. registered company in industrial automation & controls, CCHN's goal is helping saving your money by bypassing all kinds of local dealers/agents in buying industrial automation products from Chinese manufacturers directly. You will be enjoyed to get free tech support on how to choose, how to wire, how to commissioning with CCHN professional engineers. Shopping for your automation systems on CCHN one-stop online store now. The price on the website only for sample reference. for Mass order,please send the enquiry to us.

Blog

Foam cutting is a device for processing materials in the chemical industry such as foam and sponges. It mainly uses the high

...
CCHN Industry
 
Close
Shopping Categories
Search

CCHN Industry

CCHN is a trusted U.S. registered company in industrial automation & controls, CCHN's goal is helping saving your money by bypassing all kinds of local dealers/agents in buying industrial automation products from Chinese manufacturers directly. You will be enjoyed to get free tech support on how to choose, how to wire, how to commissioning with CCHN professional engineers. Shopping for your automation systems on CCHN one-stop online store now. The price on the website only for sample reference. for Mass order,please send the enquiry to us.

Blog

Foam cutting is a device for processing materials in the chemical industry such as foam and sponges. It mainly uses the high

...
32~35 Amp Thermal Overload Relay, 220V, 3-Phase
 
Close
Shopping Categories
Search

32~35 Amp Thermal Overload Relay, 220V, 3-Phase


$50.12
Affordable price thermal overload relay for sale. Current setting range 23~32 Amp or 28~35 Amp for selection, working current
SKU: CHN-TOR-3235
Free Shipping Worldwide
Delivery date: 6-12 days

Thermal overload relay features overcurrent and phase-failure protection functions. Optional current setting range 23~32 Amps or 28~35 Amps, current rating 36A, working voltage 220V~690V. 3-phase thermal relay is often used in AC motors, which is suitable for 25A contactor and 63A gG fuse breaker.

Specification

ModelCHN-JR28-36
Current Setting Range (A)23-3228-35
Matching Fuse Breaker (A)20 gG25 gG
12 aM16 aM
Matching Contactor25A
Rated Working Current (A)36A
Rated Working Voltage (V)3-phase 220V~690V
Rated Insulation Voltage (V)690V
Number of Contacts1NO + 1NC
Phase Failure Protection Functionyes
Automatic & Manual Resetyes
Temperature Compensationyes
Tripping Indicatoryes
Test Pushbuttonyes
Mounting ModePlug-in, independent
AC-15 220V Current Rating (A)2.73
AC-15 220V Current Rating (A)1.58
DC-13 220V Current Rating (A)0.2
Cross Section Area of ConductorMain CircuitSingle core or standard wire4~10 mm2
Wiring screwM4
Auxiliary CircuitSingle core or standard wire0.5~2.5 mm2
Wiring screwM3.5

 Thermal Overload Relay Applications

  • Thermal overload relays are often used in circuit protection, overload, phase failure, overtime start and locked-rotor for AC motors.
  • Thermal overload relay has functions of phase failure protection, temperature compensation, adjustable setting current, automatic or manual reset, operation indicator, NP and NO auxiliary contacts separate insulation.
  • The thermal overload relay has small installation area and various mounting methods. It has test button and stop button, which is convenient for checking the flexibility of operation.
  • The protective cover of thermal overload relay can protect fingers from electric shock. The locking device can prevent misoperation.
  • Thermal overload relay comes with remote operation, complete functions and excellent quality.

32~35 Amp Thermal Overload Relay Dimension Diagram (Unit: mm)

Dimension diagram of 32~35 Amp Thermal Overload Relay, 220V, 3-Phase

Tips: Precautions for using 35 Amp thermal overload relay.

  • 35 Amp thermal overload relay can only be used to control the overload protection of AC motors, not as short-circuit protection.
  • Before installing 35 Amp thermal overload relay, you must understand the rated current of the protected object, and the selected specification must be +20% of the rated current.
  • Usually, the 35 Amp thermal overload relay is installed directly behind the starting contactor (Magnetic Switch) of AC motor.
  • When the current is too high or the load current exceeds the setting, the 35 Amp thermal overload relay will start and disconnect the circuit. Although the path can be restored through reset button, when thermal overload relay is activated, the set current cannot be arbitrarily adjusted. The cause of overload should be found out, otherwise the protected equipment will be easily burned down.