100A 3-phase Power Line Filter, 2 Stage


$322.54
3-phase 3-wire or 3-phase 4-wire power line filter with dual stage configuration, 100 Amp rated current, 250V/440V AC rated v
SKU: CHN-EMI-20100
Free Shipping Worldwide
Delivery date: 6-12 days

100A dual-stage power line filter is available with 3-phase 3-wire or  3-phase 4-wire power system, providing strong EMI/RFI protection for various electrical equipment, including printing equipment, packaging equipment, textile equipment, industrial air conditioners, UPS, motors, servo systems, communication equipment, variable frequency device, electric drives, etc.

Specification

ModelCHN-MT720-100CHN-MT820-100
Configuration2 Stage2 Stage
Rated Current @ 40℃100A100A
Rated Voltage250/440V AC440V AC
Operating Frequency50/60Hz50/60Hz
PhaseThree Phase Three WireThree Phase Four Wire
Leakage Current (250VAC 50Hz @ 20℃)≤6.0mA≤8.0mA
Filter Range150KHz-30MHz150KHz-30MHz
Hipot Rating (one minute)Line to Line: 1450V DC
Line to Ground: 2250V DC
Line to Line: 2250V DC
Line to Neutral: 1760V DC
Line to Ground: 2700V DC
Climatic Category25/085/2125/085/21
Working Temperature-25°C~+85°C-25°C~+85°C
Output TermainalThreaded studThreaded stud
Weight3.7kg4.0kg
DimensionSee belowSee Below

Dimensions (Unit: mm)

  • 3-Phase 3-Wire Line Filter

100A 3-phase 3-wire EMI Line Filter Dimension

  • 3-Phase 4-Wire Line Filter

100A 3-phase 4-wire EMI power line filter dimensions

Electrical Schematic

  • 3-Phase 3-Wire Line Filter

3-Phase 3-Wire 2-stage Power Line Filter Electrical Schematic

  • 3-Phase 4-Wire Line Filter

100A 3-phase 4-wire EMI power line filter electrical schematic

Tips: 3 key parameters of power line filter

For EMI power line filter, rated voltage and current, pressure resistance performance, leakage current are most considered. The main evaluating performance is insertion loss.EMI power filter’s suppression capability for interference noise is evaluated by insertion loss.

  1. Standard test for insertion loss
    It is stipulated in standard measurement method, to test its insertion loss in the system with any resistance value among 50Ω~75Ω.
  2. Load test of insertion loss
    In EMI filter products, because of the unsuitable material used, it is not possible for common mode choke to guarantee fully symmetry, which would lead to saturation of magnetic rings. Meanwhile, parasitic differential mode inductor may possibly generate saturation of magnetic ring. This makes big difference between practical use and manufacturer offering data of the line filter. Therefore, load test for filter is needed.
  3. EMI filter time domain test
    Normally, for EMI line filter, we only concern about its regular performance and frequency domain suppression performance. But for EMI signal linear filter, because transmission wire itself can generate some electromagnetic interference, test signal inevitably generates some attenuation. At the time, we have to do time domain transmission performance test.