Current transformer is used to convert large currents in the AC circuit into a small proportion of current for measurement and relay protection. Current ratio 250:5A, 400:5A, 750:5A, 800:5A to1000:5A, cheap price, good quality and free shipping.
Note: The installation method of current transformer can be fixed by busbar and fixed by the bottom plate, suitable for installation in any direction. The primary conductor can be busbar or cable.
Specification:
Model | CHN-CT-60I |
Weight | 1kg |
Current Ratio (A) | VA Secondary load/ Burden (VA) | Cross-core Turn Number |
0.2 | 0.5S | 0.2S |
250-450/5 | 2.5 | 2.5 | 2.5 | 1 |
500-800/5 | 5 | 5 | 5 | 1 |
1000/5 | / | 5 | 5 | 1 |
1200-1250/5 | / | 15 | 10 | 1 |
Rated Frequency | 50/60Hz |
Rated Test Voltage | 3kV AC (1min) |
Rated Short-Time Thermal Current (ith) | 60 in |
Rated Dynamic Current (idyn) | 2.5 lth |
Rated Voltage (Um) | 0.66 kV AC |
Continuous Overload (ld) | 1.2 in |
Operating Temperature | -10℃~50℃ |
Housing Self-Extinguishing Class | VO |
Safety Factor | FS 5 |
Secondary Current | 5A/ 1A |
Bus Specification (mm)/Number | 1 |
Dimension

Model | Dimensions | Perforation size | Installation size |
W | H | D | a | e | φ | M | N |
CHN-CT-30I | 62 | 78 | 45 | 32 | 11 | 22 | 40 | 57.5 |
CHN-CT-3030I | 85 | 102 | 50 | 32 | 11 | 28 | / | 57.5 |
CHN-CT-40I | 75 | 95 | 45 | 42 | 11 | 31 | 40 | 57.5 |
CHN-CT-60I | 102 | 130 | 45 | 61.5 | 21 | 45 | 42 | 57.5 |
CHN-CT-60II | 102 | 125 | 45 | 31 | 33 | / | 42 | 57.5 |
CHN-CT-80I | 118 | 140 | 45 | 82 | 11 | 52 | 60 | 57.5 |
CHN-CT-100II | 145 | 125 | 45 | 103 | 35 | / | 80 | 57.5 |
Tips: Current Transformer Troubleshooting
- There should be no open circuit on the secondary side of the current transformer in operation. Once the open circuit occurs on the secondary side, high temperature caused by excessive iron loss may burn out the current transformer or enhance the voltage of secondary winding, thus breaking down the insulation and leading to the danger of high voltage electric shock. Therefore, when replacing a meter such as an ammeter, active power meter and reactive power meter, please ensure the current circuit in short circuit before operation. If the current transformer makes a buzz sound, please check if the internal core is loose, fasten the core bolt.
- Shell of the current transformer’s secondary side shall be grounded reliably.
- When the insulation resistance of the current transformer’s secondary side coil is lower than 10~20M ohms, drying process is required to recover the insulation before use it again.
- When the current transformer gets faults, safety operation of the primary system circuits will be affected, please report promptly to the higher authorities and heads of departments concerned to cut off the fault current transformer timely, then treatment it. As for the open circuit of secondary winding, treatments shall be implemented according to actual conditions. After necessary safety precautions are made according to relevant regulations, the current transformer can be put in use again.
Low price current transformer can select ratio 200/5A, 300/5A, 600/5A and 1000/5A. rated frequency 50Hz or 60Hz, small size and light weight, manufacturer direct sale.