Features
- Suitable for 400V AC 50Hz power supply system with rated working current 630A, 700A, 800A.
- This ATS is an intelligent self-protection transfer switch mainly including two parts - microcomputer controller and transfer switch.
- With automatic and manual operation, machinery and electrical double interlock feature.
- ATS has three switching position for options: common power ON, dual power OFF, standby power ON.
- Small size, light weight, stable performance, reliable operation and easy to use.
- Applied for residential areas, military facilities, hospitals, shopping malls, airports and so on.
Specification
Model | ZMQ2F/L-800 |
Frame Current | 800A |
Rated Operating Current (Optional) | 630A, 700A, 800A |
Number of Poles (Optional) | 3-pole | 4-pole |
Breaking Current | 35kA | 37.5kA |
Rated Operating Voltage | 400V AC |
Insulation Voltage | 2500V, no flicker and no breakdown for one minute |
Frequency | 50/60Hz |
Delay Time | 0-30s (Adjustable) |
Controller Rated Working Voltage | 230V AC |
Mechanical Life | 5,000 times |
Structural Type (Optional) | Integral type (F) or split type (L) |
Environment | Altitude | ≤2000m |
Ambient Temperature | -5℃~+40℃, the 24-hour average temperature does not exceed +35℃ |
Relative Humidity | RH≤50% @ +40℃; at a lower temperature, it is allowable to have a higher humidity. Please pay more attention to the condensation produced on the product surface with the change of humidity. |
Installation | No explosive medium, and no medium of gas and dust is enough to corrode and damage the insulation. No significant shock and vibration. |
Standards | Compliance to IEC6094-6-1, GB14048.11-2008 |
Protection Class | IP30 |
Weight | 36kg | 39kg |
Dimensions | See below |
ATS Dimensions (Unit: mm)

Type | W | W1 | L | L1 | H |
ZMQ2F/L-800/3P | 710 | 655 | 335 | 315 | 190 |
ZMQ2F/L-800/4P | 785 | 725 | 335 | 315 | 190 |
Wiring Diagram

* The above wiring diagram is just for your reference. With the different types and functions, the wiring is also different.
* When the fire takes place, EPS signal is on (provided by firefighting center) and the circuit breakers Q1 & Q2 is released or cut off.
* Q1 & Q2 refer to circuit breakers.
* KG refers to the wiring terminals.
* The R & N power ON indicator lamps are external (provided by users).
* The dashed part is supplied by users.

* 3P refers to 3-pole circuit breaker and 4P means 4-pole circuit breaker.
* 24VDC (external) is supplied by the fire control center.
Tips: Automatic transfer switch troubleshooting
1. Automatic transfer switch does not move when connected to the power, and the controller light is not on.
- Possible causes:
1. Whether the installation wiring is correct and tight;
2. Whether the fuse is blown. - Troubleshooting:
1. Check whether the circuit breaker's incoming end is loose and the wiring fails. If there is any disconnection, reconnect it.
2. For 3-pole ATS, the neutral line should be connected to the neutral terminal.
3. Replace the fuse.
2. The controller power light flashes.
- Possible causes:
1. Power failures: power overvoltage; poor power line contact; controller failure.
2. Power light blinks, buzzer alarm. - Troubleshooting:
1. Readjust the incoming line and supply voltage.
2. Check whether the incoming power supply has a loss of phase, or a loose connection.
3. Insert the controller plug again or replace the controller.
4. The neutral line and phase line of the power supply are connected reversely and reconnect it correctly again.
Reliable intelligent automatic transfer switch with microcomputer controller is best ATS for changeover between common-used power and standby power at rated working current 630 amp, 700 amp or 800 amp and rated voltage 400VAC 50Hz, adjustable 0~30s delay time, simple wiring and easy installation, high performance and long service life, suitable for residential areas, military facilities, hospitals and other areas.