185 amp 3 phase AC Magnetic Contactor, 24V/110V/220V Coil


$296.16
Low price 3 phase 3 pole AC magnetic contactor is used in electric motor control and DIN rail or panel mounting, with 24V/110
SKU: CHN-ACCON-185A
Free Shipping Worldwide
Delivery date: 6-12 days

ATO 3 pole AC magnetic contactor is used in 3 phase units. This contactor relay works between power source and high load electrical motor to balance changes in electrical frequency which may come from a power supply.

Specification

ModelCHN-CJX2-F185
Rated Currentle max AC-3 (Ue≤440V)185A
le max AC-1 (θ≤40°C)275A
Coil Rated Voltage (Optional)24V AC, 36V AC, 48V AC, 110V AC, 220V AC, 380V AC
Contact Form3NO
Auxiliary Contact (Optional)2NO, 2NC, 1NO+1NC, 2NO+2NC, 1NC+3NO, 4NO, 4NC
Frequency50Hz/ 60Hz
Rated Insulated Voltage (Ui)1000V
Rated Impulse Withstand Voltage (Uimp)8kV
Rated Operational Voltage1000V
Conventional Thermal Current (θ≤40°C)275A
Operation FrequencyAC-1, AC-2, AC-31200 times/h
AC-4300A
Rated Power (AC-3)220/240V55kW
380/400V90kW
415V100kW
440V100kW
500V110kW
660/690V110kW
1000V100kW
Connection/ WiringNumber of Lines2
Line Size25x3mm2
Cable with Splicing150mm2
Cable with Connector150mm2
Screw Diameterφ8
Tightening Torque18N.m
Standards-CompliantIEC60947-4-1, GB14048.4, EN60947-4-1
Dimensions174 x 168.5 x 181mm
Weight9.5kg

Tips: Reasons for poor contact of the AC magnetic contactor

Poor contact of the AC contactor will increase the contact resistance between the moving and static contacts, resulting in excessively high temperature of the contact surface, and causing the surface contact to become a point contact, or even non-conduction. The reasons for this failure are:  

  • There are oil stains, flower hairs, and foreign objects on the contacts.   
  • Because of long-term use, the surface of the contact is oxidized.   
  • Defects, burrs or metal swarf particles caused by arc ablation.
  • There is jamming in the moving part.