Close
Shopping Categories
Search

95 Amps 4 Pole AC Contactor 24V/110V/220V Coil


$177.89
4 pole 95 amps AC contactor has 24V/110V/220V coil volatge available for selection. When used in AC-3 380V, the rated current
SKU: ​CJX2-95
Free Shipping Worldwide
Delivery date: 6-12 days

95A 4 pole AC contactor is used under 50Hz or 60Hz, as a bypass contactor, making or breaking electric ciucuits at a long distance, frequent starting, stopping and controlling AC motors.

Specifications

ModelCJX2-95
Rated Operational Current (AC-3)380V95A
660V49A
Conventional Heating Current110A
Rated Insulation Voltage690V
Power of Controllable 3-phase Squirrel-cage Motor (AC-3)220V25kW
380V45kW
660V55kW
Operational Frequency (AC-3)Electric Life600 times/h
Mechanical Life2400 times/h
Service LifeElectric Life (104 times)60
Mechanical Life (104 times)600
Matching Fusing ModelRT16-125
Average Power Consumption (20℃) @ 50HzPick-up230VA
Holding32VA
Unit weight(kg)4P (4N/O)1.59
4P (2N/O+2N/C)1.65
Ambient Temperature-5℃~+40℃
Altittude≤2000m
Rail Size75mm
Class of PollutionClass 3
Installation Category

Dimensions (unit: mm)

4P (4NO) AC contactor

cjx2 ac contact 80004

4P (2NO+2NC) AC contactor

cjx2 ac contact 80008

Tips: The contact of AC contactor is overheating or burning for eight-hour working, how to solve?

Possible Causes:

  • Contact spring pressure is too small
  • There is oil on the contact, or the surface is uneven, and the metal particles are prominent.
  • The ambient temperature is too high or used in a closed control box
  • Copper contacts for long-term work
  • The overtravel of the contact is too small

Processing method:

  1. Increase the contact spring pressure
  2. Clean the contact surface
  3. Contactor derating
  4. Adjust the contact overtravel or replace the contact