50 Amps AC Contactor Features
The 50 Amps bypass AC contactor can control 15 kW 3-phase squirrel-cage motor under AC-3 220V, 22 kW motor under AC-3 380V, and 33kW motor under AC-3 660V. Low power consumption and widely used in various applications with frequency 50Hz/60Hz.
50 Amps AC Contactor Specifications
Model | CJX2-50 |
Rated Operational Current (AC-3) | 380V | 50A |
660V | 39A |
Conventional Heating Current | 80A |
Rated Insulation Voltage | 690V |
Power of Controllable 3-phase Squirrel-cage Motor (AC-3) | 220V | 15kW |
380V | 22kW |
660V | 33kW |
Operational Frequency (AC-3) | Electric Life | 600 times/h |
Mechanical Life | 3600 times/h |
Service Life | Electric Life (104 times) | 60 |
Mechanical Life (104 times) | 800 |
Matching Fusing Model | RT16-63 |
Average Power Consumption (20℃) @ 50Hz | Pick-up | 230VA |
Holding | 32VA |
Unit weught(kg) | 4P (4N/O) | 1.32 |
4P (2N/O+2N/C) | 1.37 |
Ambient Temperature | -5℃~+40℃ |
Altittude | ≤2000m |
Rail Size | 75mm |
Class of Pollution | Class 3 |
Installation Category | Ⅲ |
50 Amps AC Contactor Dimensions
4P (4NO) AC contact

4P (2NO+2NC) AC contact

Tips
The contactor can be divided into an AC contactor and a DC contactor according to the type of the controlled current. AC contactors are widely used as breaking and control circuits for electric power. It uses the main contact to open and close the circuit, and the auxiliary contact to execute the control command. The main contacts generally have only normally open contacts, while the auxiliary contacts often have two pairs of contacts with normally open and normally closed functions. Small contactors are often used as intermediate relays in conjunction with the main circuit.
This lightweight and convenient bypass AC contactor with 4P (4NO) or 4P (2NO+2NC) contact form, it has a lot coil voltage to choose like 24V, 110V, 220V. And when the voltage is at 380V, the rated current is 50A; voltage is at 660V, rated current is 39A. 4 pole contactor relay can be used for a long time and is also affordable.