Specification
Model | CHN-CJZ-200 |
Rated voltage | Main circuit | 1140V |
Control circuit (AC) | 36V, 220V |
Rated current | 200A |
Main contact parameter | Open distance | 2±0.2 mm |
Over distance | >1 mm |
Final power | 80±20 N |
Power frequency withstand voltage | Main circuit | 4200V |
Auxiliary circuit | 2500V |
Control circuit | 2000V |
Phase | 3 |
Number of Pole | 4 |
Frequency | AC 50Hz or 60Hz |
Making capacity | 10 le 100 times |
Breaking capacity | 8 le 25 times |
Max making & breaking capacity (A) | 2000 3 times |
Electric life | AC3 | 600000 times |
AC4 | 60000 times |
Electrical life | 1500000 times |
Function | Device protection |
Electricity type | Vacuum |
Ambient temperature | -25℃ to 40℃ |
Packaging details | Standard package or according to customer's requirements |
Weight | 6.5kg |
AC vacuum contactor outline and installation dimension (Unit: mm)

Tips: Vacuum ac contactor troubleshooting
Whether the vacuum ac contactor is faulty or not can be judged according to whether it can be closed and opened accurately and reliably and kept in the closing and opening positions. The failure of the main circuit can be found and eliminated from the routine inspection and maintenance of the vacuum ac contactor. The common failure analysis of vacuum ac contactor is as follows:
- Inability to store energy: Inability to store energy is one of the common failures of vacuum contactors, especially the energy storage mechanism driven by ratchets and pawls has a higher probability of failure. The energy storage mechanism to complete the energy storage action mainly depends on the three links of the energy storage motor, the drive mechanism, and the positioning parts. Grasping these three links firmly, it is easy to find out the cause of the ac vacuum contactor failure.
- No closing action: The fault here is mainly related to whether the closing electromagnet is closed, whether the energy storage is in place, and whether the positioning member is operating normally.
- The ac vacuum contactor has a closing action but fails to close. When analyzing this type of failure, you should first analyze the lock, and then analyze whether it is related to the energy storage part.
- The ac vacuum contactor does not open: It should be emphasized here that when the vacuum ac contactor refuses to move or closes, before analyzing and repairing the main body of the contactor, it is necessary to fully judge whether the reason is in the control and secondary components such as auxiliary switches, terminal blocks, etc., and then analyze and diagnose the contactor.
Rated 1140V, 200A ac vacuum contactor is used for frequently switch on and off the normal working current. 3 phase, 36 volt or 220 volt control circuit, 2±0.2 mm open distance, 80±20 N final power, 1500000 times electrical life.