1/2 hp VFD, 0.4 kW, 208V - 240V single phase to three phase variable frequency drive, sale by manufacturer directly.
Specification:
Basics | Model | GK3000-2S0004 |
Capacity | 1/2 hp (0.4 kW) |
Shipping weight | 2 kg |
Dimension | 142*85*110 mm |
I/O Feature | Rated current | 3 A |
Input voltage | 1 phase 220~240V AC |
Input frequency | 50Hz/ 60Hz |
Output voltage | 3 phase AC 0~input voltage |
Output frequency | 0.00~400.00Hz |
Over load capacity | 150% of rated current for 1 minute, 180% of rated current for 3 seconds |
Control Feature | Control mode | V/F control; Sensorless vector control; |
Communication | RS485 |
Speed regulation | 1:100 |
Start torque | 150% of rating torque at 1 Hz |
Speed control accuracy | ≤±0.5% of rating synchronous speed |
Frequency precision | Digital setting: max frequency x± 0.01%; Analog setting: max frequency x± 0.2% |
Frequency resolution | Analog setting: 0.1% of max frequency; Digital setting: 0.01Hz |
Torque boost | Automatic torque boost, manual torque boost 0.1%~30.0% |
Interior PID controller | Be convenient to make closed-loop system |
Automatic energy save running | Optimize V/F curve automatically based on the load to realize power save running |
Automatic voltage regulation (AVR) | Can keep constant output voltage when power source voltage varies. |
Automatic current limiting | Limit running current automatically to avoid frequent over-current which will cause trip |
Environment | Enclosure rating | IP 20 |
Temperature | –10℃~ +40℃; VFD will be derated if ambient temperature exceed 40℃; each rise 1℃, the derate will be 5% |
Humidity | 5%-95%, without condensation |
Altitude | ≤1000m; VFD will be derated if above 1000m |
Impingement and oscillation | Normal running:<5.9m/s2 (0.6g); Transportation:<15m/s2 (1.5g) |
Store environment | –20℃~ +60℃; no dust, no corrosive gas, no direct sunlight |
Tips: Variable frequency drive hardware replacement precautions
- Replace the IGBT. Measure whether the resistance value of each road is balanced.
- Replace the drive board. Need to carefully check whether the plug and socket number is consistent.
- Replace the main control board. After replacing the main control board, set the application parameters, motor parameters and protection parameters of VFD.
- Replace the PG card. Check whether the terminals are normal. If the motor has a vibration or cannot rotate after replacing the card, need to exchange the A and B phase.
- Replace the communication board. Simply check the DIP switch set by VFD hardware station number, and then check that the communication light is normal.
- The communication board of some VFD series is an independent CPU. After the replacement, need to upload configuration program.
1/2 hp VFD, convert single phase to three phase for AC motor speed controls, 208V - 240V 3 amps, IP20, RS485 enabled, manufacturer direct sale.